| Input Voltage |
Nominal Voltage +/- 15% |
|
| Output Voltage |
Nominal Voltage +/- 5% or +/- 3% |
|
| Regulation With Respect to the Load |
+/- 1% from zero to full load |
|
| Correction Time |
One cycle time, maximum (16.6 miliseconds) |
|
| Operating Frecuency |
60 Hz +/- 10% |
|
| Overload Capability |
400% of nominal load on startup |
|
| Protection Against Over and Undervoltages |
Varistors on the output terminals (protecting against short duration peaks) and output load shedding contactor (protecting against long periods of over and under voltages on the output) |
|
| Efficiency |
98% operating efficiency, worst case |
|
| Output Waveform Distorsion |
Less than 0.5% THD |
|
| Protection Against Current Overload |
Thermomagnetic circuit breaker on the input |
|
| Control |
Totally solid state |
|
| Quality |
Industrial grade |
|
| Operating Temperature |
From 0 to 40 degrees Celsius |
|
| Cabinet |
Sheet steel with baked enamel finish |